4 |
Dispensers - hose breakaways are missing or leaking - Missing breakaway. |
1, 2, 4 |
Line interstitial sensors have been raised and rendered inoperational. - Tank 4 Diesel STP, E-85 STP, RUL STP, and Disp. 7 |
1 |
Miscellaneous - All equipment and other items shall be maintained in accordance with 41 Ill. Adm. Code 174 through 176 and manufacturer's instructions and otherwise shall be kept in good operating condition at all times. Reference 176.410 |
1, 2, 3, 4, 5 |
Piping interstitial must be open in all sumps - The dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) (All Dispensers) |
1, 2, 3, 4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |