Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2045148
Status: Active
Facility Name: Meijer
Address: 9202 S. Western Ave.
Evergreen Park, IL 60620
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003064
Green Tag Issue Date: 10/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Meijer Great Lakes Limited Partnership
Owner Address: 2929 Walker Avenue, NW
Grand Rapids, MI 495449428
Owner Status: Current Owner
Purchase Date: 6/1/2013
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 8/1/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0023695 Meijer Great Lakes Limited Partnership Current Owner 6/1/2013

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250549 (Pending)    Issue Date: 3/4/2025    Expiration Date: 5/3/2025    View NOV Form

Tanks Violation
4 Dispensers - hose breakaways are missing or leaking - Missing breakaway.
1, 2, 4 Line interstitial sensors have been raised and rendered inoperational. - Tank 4 Diesel STP, E-85 STP, RUL STP, and Disp. 7
1 Miscellaneous - All equipment and other items shall be maintained in accordance with 41 Ill. Adm. Code 174 through 176 and manufacturer's instructions and otherwise shall be kept in good operating condition at all times. Reference 176.410
1, 2, 3, 4, 5 Piping interstitial must be open in all sumps - The dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) (All Dispensers)
1, 2, 3, 4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 20000 Gasoline - Regular Currently in use Federal
2 8000 Gasoline - Premium Currently in use Federal
3 8000 E85 Currently in use Federal
4 8000 Diesel Fuel Currently in use Federal
5 6000 Diesel Fuel Currently in use Federal

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms

No Forms Found