Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 11-1006 |
9/22/2011 |
Removal Log |
00913-2011REM |
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
9/22/2011 |
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/3/2015 |
|
Abandoned Material: |
|
| Current Age: |
11 |
|
Abandoned Date: |
|
| Install Date: |
5/15/2015 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/28/2025 |
10/28/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
10/28/2025 |
10/28/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/30/2026 |
1/30/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
10/28/2025 |
10/28/2028 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/28/2025 |
10/28/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
10/28/2025 |
10/28/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/28/2025 |
10/28/2028 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/28/2025
|
Tank Number 3
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/3/2015 |
|
Abandoned Material: |
|
| Current Age: |
11 |
|
Abandoned Date: |
|
| Install Date: |
5/15/2015 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/28/2025 |
10/28/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
10/28/2025 |
10/28/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/28/2025 |
10/28/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/20/2022 |
5/20/2025 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/28/2025 |
10/28/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
10/28/2025 |
10/28/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/28/2025 |
10/28/2028 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/28/2025
|
Tank Number 4
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/3/2015 |
|
Abandoned Material: |
|
| Current Age: |
11 |
|
Abandoned Date: |
|
| Install Date: |
5/15/2015 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/28/2025 |
10/28/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 with CSLD |
10/28/2025 |
10/28/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/28/2025 |
10/28/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
10/28/2025 |
10/28/2028 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/28/2025 |
10/28/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
10/28/2025 |
10/28/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/28/2025 |
10/28/2028 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/28/2025
|
|
Tank
|
Fiberglass Double Wall XERXES
|
Precision Test (Tank)
|
Pass
|
9/30/2019
|
Tank Number 5
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Unknown |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
8/4/2015 |
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found