Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2044984
Status: Active
Facility Name: Waterway's Gas and Wash
Address: 2370 Waukegan Rd Northbrook, IL 60062
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003282
Green Tag Issue Date: 11/15/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Waterway Gas and Wash Company
Owner Address: 727 Goddard Avenue Chesterfield, MO 63005
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/26/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/15/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037694 Waterway Gas and Wash Company Current Owner
U0027346 Hamilton Partners Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252768 (Pending)    Issue Date: 10/20/2025    Expiration Date: 12/19/2025    View NOV Form

Tanks Violations
2, 3, 4 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
2, 3, 4 Annual leak detection certification not completed (Required annually).
2, 3, 4 Line interstitial sensor functional test not accomplished (Required annually).
4 Miscellaneous - Sump sensors not installed per manufacturer's recommendations 175.640.a.2
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
2, 3, 4 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
2, 3, 4 Piping interstitial must be open in all sumps - UDC's & STP's
2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2, 3, 4 Tank interstitial sensor functional test not accomplished (Required annually).
2, 3, 4 Triennial spill prevention equipment testing not completed.
2, 3, 4 Triennial testing for qualifying piping containment sump not completed (Required every 3 years).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
11-1006 9/22/2011 Removal Log 00913-2011REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 1000 Heating Oil Removed State 09/22/2011 - REM
2 20000 Gasoline - Regular Currently in use Federal
3 12000 Gasoline - Premium Currently in use Federal
4 8000 Diesel Fuel Currently in use Federal
5 1000 Unknown Removed Exempt $0.00 08/04/2015 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active

MFD Motorfuel Dispensing Forms

No Forms Found