Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2044529
Status: Active
Facility Name: Circle K #6870
Address: 2832 S. Route 59
Naperville, IL 60564
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001702
Green Tag Issue Date: 1/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 11/14/2011
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 11/14/2011
U0033589 Jewel Food Stores, Inc. Former Owner 9/17/2009

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250732 (Pending)    Issue Date: 3/19/2025    Expiration Date: 5/18/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
4 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Repair/replace Premium STP Tank top lid and ring. Equipment in disrepair. Reference 176.410
Facility Facility Operation and Maintenance Plan not completed or available.
4 Install or replace lockable fill pipe caps. - All equipment and other items shall be maintained in accordance with 41 Ill. Adm. Code 174 through 176 and manufacturer's instructions and otherwise shall be kept in good operating condition at all times. Reference 176.410 (Test ports on Impact valves need to be taken off impact. RUL and PUL, dispenser 5/6)
2 Miscellaneous - E85 fill cap missing rubber o-ring
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan
1 Open electrical conduit or junction boxes. - Located under lid next to the Regular Fill. For tank probe wire.
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

NOV Number: E0020250744 (Pending)    Issue Date: 3/19/2025    Expiration Date: 5/18/2025    View NOV Form

Tanks Violation
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2009 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 12/9/2009 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/30/2024 5/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 5/30/2024 5/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/30/2024 5/30/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 5/30/2024 5/30/2027
Overfill Prev Device Overfill Drop Tube Valve 5/30/2024 5/30/2027
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 6/28/2024 6/28/2027
Leak Detect - Piping Stand Alone Sump Sensor 5/30/2024 5/30/2025
Spill Contain Device Double Wall Spill Bucket 5/30/2024 5/30/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 5/30/2024



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2009 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 12/9/2009 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/25/2024 11/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 5/30/2024 5/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/30/2024 5/30/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 5/30/2024 5/30/2027
Overfill Prev Device Overfill Drop Tube Valve 5/30/2024 5/30/2027
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 6/28/2024 6/28/2027
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 6/20/2023 6/20/2024
Leak Detect - Piping Stand Alone Sump Sensor 5/30/2024 5/30/2025
Spill Contain Device Double Wall Spill Bucket 5/30/2024 5/30/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 5/30/2024



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2009 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 12/9/2009 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/30/2024 5/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 5/30/2024 5/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/30/2024 5/30/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 5/30/2024 5/30/2027
Overfill Prev Device Overfill Drop Tube Valve 5/30/2024 5/30/2027
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 6/28/2024 6/28/2027
Leak Detect - Piping Stand Alone Sump Sensor 5/30/2024 5/30/2025
Spill Contain Device Double Wall Spill Bucket 5/30/2024 5/30/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 5/30/2024



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/15/2009 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 12/9/2009 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/30/2024 5/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 5/30/2024 5/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/30/2024 5/30/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 5/30/2024 5/30/2027
Overfill Prev Device Overfill Drop Tube Valve 7/19/2024 7/19/2027
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 6/28/2024 6/28/2027
Leak Detect - Piping Stand Alone Sump Sensor 5/30/2024 5/30/2025
Spill Contain Device Double Wall Spill Bucket 5/30/2024 5/30/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 5/30/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/28/2024 6/28/2027
Leak Detect - Piping Sump Sensor 5/30/2024 5/30/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/28/2024 6/28/2027
Leak Detect - Piping Sump Sensor 5/30/2024 5/30/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/28/2024 6/28/2027
Leak Detect - Piping Sump Sensor 5/30/2024 5/30/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/28/2024 6/28/2027
Leak Detect - Piping Sump Sensor 5/30/2024 5/30/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/28/2024 6/28/2027
Leak Detect - Piping Sump Sensor 5/30/2024 5/30/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/28/2024 6/28/2027
Leak Detect - Piping Sump Sensor 5/30/2024 5/30/2025

MFD Motorfuel Dispensing Forms

No Forms Found