Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2044046
Status: Active
Facility Name: D Construction
Address: 2115 Moen Avenue Rockdale, IL 60436
County: Will
Property Parcel: 30-07-19-100-060-0000
Facility Type: Commercial / Retail
Owner Type: Private
Green Tag Decal: Z003784
Green Tag Issue Date: 3/14/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: D Construction, Inc.
Owner Address: 1488 So. Broadway Coal City, IL 60416
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 9/18/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0025555 D Construction, Inc. Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261392 (Pending)    Issue Date: 5/22/2026    Expiration Date: 7/21/2026    View NOV Form

Tanks Violations
1, 2 Annual electronic line leak detector test not completed.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Dispensers - hoses cracked, split or worn and require replacement - Dispenser 1 hose is kinked and labeled with out of service tape.
Facility Facility Operation and Maintenance Plan not completed or available. - Form available at: https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html
Facility Miscellaneous
Facility Missing copies of 30 day Walkthrough Inspection Report. - Form available at: https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html
Facility Missing copies of Annual Walkthrough Inspection Report. - Form available at: https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html
Facility Missing copy of emergency instructions or emergency procedures plan - Form available at: https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html
Facility Missing list of designated Class A/B & C Operators - Form available at: https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html
Facility Submit Notification Form for Ownership Change
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).
1, 2 Verify and test piping sump sensor for positive shutdown - Testing for tank 1 STP, tank 2 STP, dispenser 1/2, and dispenser 3/4 not completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/2/2008 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 8/1/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/1/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/15/2025 4/15/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/15/2025 4/15/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/15/2025 4/15/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 4/15/2025 4/15/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Double Wall STP/Tanktop Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2026
Spill Contain Device Single Wall Spill Bucket 4/15/2025 4/15/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 4/15/2025



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/2/2008 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 8/1/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/1/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/15/2025 4/15/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/15/2025 4/15/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/15/2025 4/15/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 4/15/2025 4/15/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Double Wall STP/Tanktop Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2026
Spill Contain Device Single Wall Spill Bucket 4/15/2025 4/15/2028
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 4/15/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2026

MFD Motorfuel Dispensing Forms

No Forms Found