Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2043694
Status: Active
Facility Name: IL0064
Address: 3328 W. 159th Street
Markham, IL 60428
County: Cook
Property Parcel: 28-14-429-032-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001298
Green Tag Issue Date: 6/10/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Lehigh Gas Wholesale Services
Owner Address: 645 Hamilton, Suite 400
Allentown, PA 18101
Owner Status: Current Owner
Purchase Date: 9/27/2016
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 6/12/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/10/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037337 Lehigh Gas Wholesale Services Current Owner 9/27/2016
U0025164 BAPA, LLC & PT, LLC Former Owner 10/2/2014
U0037164 Preferred Real Estate Investments, LLC Former Owner 5/2/2012
U0035843 Ash's Gas 2, Inc. Former Owner
U0034204 Al-Qawasmi, Faud Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250561 (Pending)    Issue Date: 3/5/2025    Expiration Date: 5/4/2025    View NOV Form

Tanks Violation
1, 2, 3 Miscellaneous - Adequate collision protection to protect against physical damage shall be provided for vent piping. 175.440a)8)
3 Not Vented Properly - Vent was hit and damaged. Repair/replace and retest vent.

NOV Number: E0020250562 (Pending)    Issue Date: 3/5/2025    Expiration Date: 5/4/2025    View NOV Form

Tanks Violation
Facility LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Provide appropriate collision protection for LP tank cage. Refer to OSFM Rules section 175.210 q) for proper placement of collision protection.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/12/2008 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 11/9/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/28/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/28/2025 1/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/28/2025 1/28/2026
Overfill Prev Device Overfill Drop Tube Valve 2/26/2024 2/26/2027
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/12/2024 4/12/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 1/28/2025



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/12/2008 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 11/9/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/28/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/28/2025 1/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/28/2025 1/28/2026
Overfill Prev Device Overfill Drop Tube Valve 2/26/2024 2/26/2027
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 4/12/2024 4/12/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 1/28/2025



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/12/2008 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 11/9/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/28/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/28/2025 1/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/28/2025 1/28/2026
Overfill Prev Device Overfill Drop Tube Valve 2/26/2024 2/26/2027
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 4/12/2024 4/12/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 1/28/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found