Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0033767 |
Richmond Petroleum, Inc. |
Current Owner |
8/15/2007 |
| U0034227 |
Access Development Group |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020262257
(Pending)
Issue Date:
9/25/2026
Expiration Date:
11/24/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view. |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Self-service instructional signs at dispensers are missing or do not meet minimum requirements. Install appropriate signage. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 07-0949 |
7/11/2007 |
Removal Log |
00944-2007REM |
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/4/2008 |
|
Abandoned Material: |
|
| Current Age: |
18 |
|
Abandoned Date: |
|
| Install Date: |
8/15/2007 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/25/2008 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/14/2026 |
5/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/14/2026 |
5/14/2029 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
5/14/2026 |
5/14/2029 |
Leak Detect - Piping
|
Sump Sensor |
5/14/2026 |
5/14/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/14/2026 |
5/14/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
|
Tank
|
Fiberglass Double Wall XERXES
|
Precision Test (Tank)
|
Pass
|
5/20/2024
|
Tank Number 2
| Capacity: |
5000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/4/2008 |
|
Abandoned Material: |
|
| Current Age: |
18 |
|
Abandoned Date: |
|
| Install Date: |
8/15/2007 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/25/2008 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/14/2026 |
5/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/14/2026 |
5/14/2029 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
5/14/2026 |
5/14/2029 |
Leak Detect - Piping
|
Sump Sensor |
5/14/2026 |
5/14/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/14/2026 |
5/14/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
|
Tank
|
Fiberglass Double Wall XERXES
|
Precision Test (Tank)
|
Pass
|
5/20/2024
|
Tank Number 3
| Capacity: |
5000 |
|
Petroleum Use: |
|
| Product: |
E85 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/4/2008 |
|
Abandoned Material: |
|
| Current Age: |
18 |
|
Abandoned Date: |
|
| Install Date: |
8/15/2007 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/25/2008 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/14/2026 |
5/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/14/2026 |
5/14/2029 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
5/14/2026 |
5/14/2029 |
Leak Detect - Piping
|
Sump Sensor |
5/14/2026 |
5/14/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/14/2026 |
5/14/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
|
Tank
|
Fiberglass Double Wall XERXES
|
Precision Test (Tank)
|
Pass
|
5/20/2024
|
Tank Number 4
| Capacity: |
5000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/4/2008 |
|
Abandoned Material: |
|
| Current Age: |
18 |
|
Abandoned Date: |
|
| Install Date: |
8/15/2007 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/25/2008 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/14/2026 |
5/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
5/14/2026 |
5/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/14/2026 |
5/14/2029 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
5/14/2026 |
5/14/2029 |
Leak Detect - Piping
|
Sump Sensor |
5/14/2026 |
5/14/2029 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
5/14/2026 |
5/14/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
5/14/2026
|
|
Tank
|
Fiberglass Double Wall XERXES
|
Precision Test (Tank)
|
Pass
|
5/20/2024
|
Tank Number 5
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
7/11/2007 |
|
OSFM
First Notify Date: |
8/6/2007 |
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
7/11/2007 |
|
OSFM
First Notify Date: |
8/6/2007 |
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
7/11/2007 |
|
OSFM
First Notify Date: |
8/6/2007 |
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
5/14/2026
|
5/14/2029
|
Leak Detect - Piping
|
Sump Sensor |
5/14/2026
|
5/14/2027
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
5/14/2026
|
5/14/2029
|
Leak Detect - Piping
|
Sump Sensor |
5/14/2026
|
5/14/2027
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
5/14/2026
|
5/14/2029
|
Leak Detect - Piping
|
Sump Sensor |
5/14/2026
|
5/14/2027
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
5/14/2026
|
5/14/2029
|
Leak Detect - Piping
|
Sump Sensor |
5/14/2026
|
5/14/2027
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found