Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2043201
Status: Active
Facility Name: Circle K #6754
Address: 1505 Butterfield Road
Aurora, IL 60507
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002409
Green Tag Issue Date: 2/1/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/1/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251221 (Pending)    Issue Date: 5/8/2025    Expiration Date: 7/7/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020251222 (Pending)    Issue Date: 5/8/2025    Expiration Date: 7/7/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site.
1, 2, 3 Miscellaneous - Sensors that are in dispenser sumps are stand alone sensors.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site.
1, 2, 3 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 20000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Premium Currently in use Federal $0.00
3 8000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms