Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042507
Status: Active
Facility Name: Vernon Hills Data Center
Address: 475 Corporate Woods Parkway Vernon Hills, IL 60061
County: Lake
Property Parcel:
Facility Type: Commercial / Retail
Owner Type: Private
Green Tag Decal: Z003554
Green Tag Issue Date: 8/22/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: HSBC Technology & Services (USA), Inc.
Owner Address: 2929 Walden Ave. Depew, NY 14043
Owner Status: Current Owner
Purchase Date: 9/15/2015
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/22/2025

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038779 HSBC Technology & Services (USA), Inc. Current Owner 9/15/2015
U0007035 Household Finance Corporation III Former Owner 1/1/2005
U0036001 HSBC Finance Corporation Former Owner
U0034826 Household Finance Corporation III Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 30000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/17/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/19/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/20/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/18/2024 12/18/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/18/2024 12/18/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/18/2024 12/18/2025
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 12/18/2024 12/18/2025
Overfill Prev Device Overfill Drop Tube Valve 12/14/2023 12/14/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/14/2023 12/14/2026
Leak Detect - Piping Sump Sensor 12/18/2024 12/18/2025
Piping Single Wall STP/Tanktop Sump 12/14/2023 12/14/2026
Leak Detect - Piping Sump Sensor 12/18/2024 12/18/2025
Spill Contain Device Single Wall Spill Bucket 12/14/2023 12/14/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 12/18/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/18/2024



Tank Number 2

Capacity: 30000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/17/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 2/9/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/10/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/18/2024 12/18/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/18/2024 12/18/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/18/2024 12/18/2025
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 12/18/2024 12/18/2025
Overfill Prev Device Overfill Drop Tube Valve 12/14/2023 12/14/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/14/2023 12/14/2026
Leak Detect - Piping Sump Sensor 12/18/2024 12/18/2025
Piping Single Wall STP/Tanktop Sump 12/14/2023 12/14/2026
Leak Detect - Piping Sump Sensor 12/18/2024 12/18/2025
Spill Contain Device Single Wall Spill Bucket 12/14/2023 12/14/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 12/18/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/18/2024

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found