Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042187
Status: Active
Facility Name: Orchard Property 2, LLC
Address: 1700 Orchard Road Montgomery, IL 60538
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003380
Green Tag Issue Date: 1/4/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Orchard Property 2, LLC
Owner Address: 1700 Orchard Road Montgomery, IL 60538
Owner Status: Current Owner
Purchase Date: 7/1/2004
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/29/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0031988 Orchard Property 2, LLC Current Owner 7/1/2004

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252407 (Pending)    Issue Date: 9/16/2025    Expiration Date: 11/15/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020252408 (Pending)    Issue Date: 9/16/2025    Expiration Date: 11/15/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose on regular dispenser 1 and diesel dispenser 3.
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
Facility Miscellaneous - Center bollard is bent down. Repair or replace center west bollard.
Facility Miscellaneous - Exterior emergency shut off switch sign is hard to read. Replace sign.
2 Miscellaneous - ATG shows L3 Fuel Alarm.
3 Miscellaneous - Premium fill cover is broken.
Facility Missing copies of 30 day Walkthrough Inspection Report. - OSFM 30 day walkthrough form is required to be completed monthly.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
1, 2, 3 Monthly line interstitial sensor records not available. - 2025 liquid status is missing.
1, 2, 3 Precision line test required. - Since monthly liquid status report is missing a precision line test is required.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
1, 2, 3 Triennial spill prevention equipment testing not completed. - Section 175.405 Spill Containment and Overfill Prevention Equipment b) Owners and operators of UST systems with spill and overfill prevention equipment must meet the requirements of subsections (b) and (c) and shall ensure the equipment is operating properly and will prevent releases to the environment. Spill prevention equipment (such as a catchment basin, spill bucket, or other spill containment device) must prevent releases to the environment by being tested at installation, immediately after any repairs, and at least once every three years to ensure the equipment is liquid tight by using vacuum, pressure or liquid testing in accordance with one of the following criteria: 1A) Requirements developed by the manufacturer of the spill prevention equipment. Owners and operators may use this option only if the manufacturer has developed requirements; 2B) Requirements developed by the manufacturer of the testing equipment; or 3C) A hydrostatic test that meets the requirements of Section 175.410(j).
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All UDC sumps.
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Tanks 1 and 3 STP sumps.
2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All UDC sumps.
3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Tanks 1 and 3 STP sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 7/1/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/4/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/27/2025 9/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/27/2025 9/27/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 9/27/2025 9/27/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor 9/27/2025 9/27/2026
Spill Contain Device Single Wall Spill Bucket 9/27/2025 9/27/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/27/2025
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 8/10/2023



Tank Number 2

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 7/1/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/4/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/27/2025 9/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/27/2025 9/27/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 9/27/2025 9/27/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor 9/27/2025 9/27/2026
Spill Contain Device Single Wall Spill Bucket 9/27/2025 9/27/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/27/2025
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 8/10/2023



Tank Number 3

Capacity: 8000 Petroleum Use: None
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 7/1/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/4/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/27/2025 9/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/27/2025 9/27/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Alarm 9/27/2025 9/27/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Galvanized Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor 9/27/2025 9/27/2026
Spill Contain Device Single Wall Spill Bucket 9/27/2025 9/27/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/27/2025
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 9/27/2025
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 8/10/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028



Name\ID 18S/19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 19S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2025 9/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/27/2025 9/27/2026

MFD Motorfuel Dispensing Forms

No Forms Found