Tanks |
Violation |
2 |
Line leak detection equipment in alarm or failed test, must repair or replace. - SENSOR IS IN ALARM AT THE PREMIUM STP |
1, 2 |
Precision line test required. - PUMP # 7 HAS A WEEPING LEAK AT THE SHEAR VALVE / UNION LOCATION |
1, 2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |
1, 2 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress |