Notice of Violations (Current)
NOV Number:
E0020250164
(Pending)
Issue Date:
1/22/2025
Expiration Date:
3/23/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020250165
(Pending)
Issue Date:
1/22/2025
Expiration Date:
3/23/2025
View NOV Form
Tanks |
Violation |
Facility |
Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan does not meet requirements of new rules or is not available. Go to https://sfm.illinois.gov to download and complete O & M template and maintain completed form on site. |
Facility |
Miscellaneous - Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) (Inside E-stop not labeled) |
1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispensers sumps 1/2 and 9/10 failed testing on 8/8/2024. Need to repair/replace and retest. |