Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042046
Status: Active
Facility Name: Jefferson BP
Address: 1987 W. Jefferson Joliet, IL 60435
County: Will
Property Parcel: 07-07-304-017
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA01970
Green Tag Issue Date: 7/3/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: YNZ Enterprises, Inc.
Owner Address: 1987 W. Jefferson Street Joliet, IL 60435
Owner Status: Current Owner
Purchase Date: 6/23/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/27/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/3/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039581 YNZ Enterprises, Inc. Current Owner 6/23/2023
U0035189 PAV 2, LLC, Former Owner 12/5/2013
U0033882 Joliet Petroleum, LLC Former Owner 11/20/2006
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00728-2025UPG Upgrade Approved / Issued 6/11/2025 6/15/2025 12/16/2025 Documents

Notice of Violatlions (Current)

NOV Number: E0020252055 (Pending)    Issue Date: 8/12/2025    Expiration Date: 10/11/2025    View NOV Form

Tanks Violations
2 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Drop tube valve for tank 2 failed test on 8/6/2025.
1, 2 Verify and test piping sump sensor for positive shutdown - Sump sensor for dispenser 5/6 failed test on 8/6/2025. Repair or replace.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/27/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 6/3/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/16/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/15/2024 8/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/15/2024 8/15/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/15/2024 8/15/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/10/2023 3/10/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025
Spill Contain Device Single Wall Spill Bucket 8/15/2024 8/15/2027
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 3/10/2023
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 6/29/2020



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/27/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 6/3/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/16/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/28/2025 5/28/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/15/2024 8/15/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/15/2024 8/15/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/10/2023 8/6/2025
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025
Spill Contain Device Double Wall Spill Bucket 6/14/2025 6/14/2028
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 3/10/2023
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 6/29/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/6/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/15/2024 8/15/2027
Leak Detect - Piping Sump Sensor 8/15/2024 8/15/2025

MFD Motorfuel Dispensing Forms

No Forms Found