Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2041801
Status: Active
Facility Name: Citgo
Address: 1053 W. 103rd Street
Chicago, IL 60649
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002478
Green Tag Issue Date: 9/20/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Chicago Property on 103rd, LLC
Owner Address: 103 W. 103rd Street
Chicago, IL 60643
Owner Status: Current Owner
Purchase Date: 5/1/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 9/20/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/20/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038560 Chicago Property on 103rd, LLC Current Owner 5/1/2016
U0033809 Aberdeen Citgo, Inc. Former Owner 5/1/2016
U0032754 Aniyan Vargthese Former Owner 10/13/2004
U0031412 Shahloul, Mazen Former Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251107 (Pending)    Issue Date: 4/23/2025    Expiration Date: 6/22/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Line interstitial sensor functional test not accomplished (Required annually). - STP & Dispenser Sump Sensors
1, 2 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).
1, 2 Triennial spill prevention equipment testing not completed.
1, 2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP & Dispenser Sumps

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/27/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 8/28/2003 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/28/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/28/2024 2/28/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 2/28/2024 2/28/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/28/2024 2/28/2025
Overfill Prev Device Overfill Drop Tube Valve 2/28/2024 2/28/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/20/2022 4/20/2025
Leak Detect - Piping Non-Discriminating Sump Sensor 1/1/2019 11/11/2019
Leak Detect - Piping Sump Sensor 2/28/2024 2/28/2025
Spill Contain Device Single Wall Spill Bucket 4/20/2022 4/20/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 2/28/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/27/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 8/28/2003 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/28/2003

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/28/2024 2/28/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 2/28/2024 2/28/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/28/2024 2/28/2025
Overfill Prev Device Overfill Drop Tube Valve 2/28/2024 2/28/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 9/18/2024 9/18/2027
Leak Detect - Piping Sump Sensor 2/28/2024 2/28/2025
Spill Contain Device Single Wall Spill Bucket 7/8/2022 7/8/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 2/28/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/20/2022 4/20/2025
Leak Detect - Piping Sump Sensor 2/28/2024 2/28/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/20/2022 4/20/2025
Leak Detect - Piping Sump Sensor 2/28/2024 2/28/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/8/2022 7/8/2025
Leak Detect - Piping Sump Sensor 2/28/2024 2/28/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/20/2022 4/20/2025
Leak Detect - Piping Sump Sensor 2/28/2024 2/28/2025

MFD Motorfuel Dispensing Forms

No Forms Found