Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2041801
Status: Active
Facility Name: Citgo
Address: 1053 W. 103rd Street
Chicago, IL 60649
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002198
Green Tag Issue Date: 7/13/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Chicago Property on 103rd, LLC
Owner Address: 103 W. 103rd Street
Chicago, IL 60643
Owner Status: Current Owner
Purchase Date: 5/1/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/18/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/15/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038560 Chicago Property on 103rd, LLC Current Owner 5/1/2016
U0033809 Aberdeen Citgo, Inc. Former Owner 5/1/2016
U0032754 Aniyan Vargthese Former Owner 10/13/2004
U0031412 Shahloul, Mazen Former Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240199 (Pending)    Issue Date: 1/24/2024    Expiration Date: 3/24/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Line interstitial sensor functional test not accomplished (Required annually). - STP Sump Sensors and Dispenser Sump Sensors
2 Line interstitial sensors have been raised and rendered inoperational. - Lower Regular STP Sump Sensor
1, 2 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).
2 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Regular STP Sump

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline - Premium Currently in use Federal $0.00
2 12000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found