Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Missing lid cover on STP Sump |
1, 2 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Fuel Alarm on Regular & Premium STP Sump Sensors |
Facility |
Miscellaneous - 41 Ill. Adm. Code Section 175.210 (d )(3) Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. |
1, 2 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2 |
Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. |
1, 2 |
Triennial spill prevention equipment testing not completed. |
2 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Regular STP Sump |
1, 2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP Sumps |