Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2041738
Status: Active
Facility Name: Marquette Mobil
Address: 7200 S. Western Avenue
Chicago, IL 60636
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002183
Green Tag Issue Date: 11/2/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Western Seventy Two, LLC
Owner Address: 7200 S. Western Ave.
Chicago, IL 60636
Owner Status: Current Owner
Purchase Date: 9/15/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/28/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/2/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041205 Western Seventy Two, LLC Current Owner 9/15/2023
U0031352 7200 S. Western, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251170 (Pending)    Issue Date: 5/5/2025    Expiration Date: 7/4/2025    View NOV Form

Tanks Violation
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Missing lid cover on STP Sump
1, 2 Line leak detection equipment in alarm or failed test, must repair or replace. - Fuel Alarm on Regular & Premium STP Sump Sensors
Facility Miscellaneous - 41 Ill. Adm. Code Section 175.210 (d )(3) Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick.
1, 2 Triennial spill prevention equipment testing not completed.
2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Regular STP Sump
1, 2 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP Sumps

NOV Number: E0020251171 (Pending)    Issue Date: 5/5/2025    Expiration Date: 7/4/2025    View NOV Form

Tanks Violation
Facility Fire Extinguishers - Past due for annual testing

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline - Premium Currently in use Federal $0.00
2 12000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms