Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2041609
Status: Active
Facility Name: Circle K #6822
Address: 160 Douglas Road
Oswego, IL 60543
County: Kendall
Property Parcel: 03-03-151-023
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003361
Green Tag Issue Date: 11/22/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 11/14/2011
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/22/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 11/14/2011
U0033589 Jewel Food Stores, Inc. Former Owner 6/2/2006
U0028677 Albertson's, Inc. Former Owner 1/1/2003
U0022589 Kellebrew Trucking Inc Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250572 (Pending)    Issue Date: 3/5/2025    Expiration Date: 5/4/2025    View NOV Form

Tanks Violation
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - 175.210 g) All dispensing units shall be readily visible from the control station without assistive devices. However, as an alternative, in the event that the attendant's view of a dispenser is permanently obstructed, or if a dispenser is located so that activity at the dispenser is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. The cameras shall be allowed to sweep to provide a view of multiple dispensing locations, but must provide a view on the screen of each dispensing unit at least every 30 seconds. In lieu of the closed-circuit camera, the facility may elect to have an emergency stop that shall be located at least 20 and not more than 50 feet from the dispenser that has a permanently obstructed view. Using an emergency stop in lieu of the closed circuit camera pursuant to this subsection (g) must be approved in advance by OSFM. If a closed-circuit camera or viewing screen is inoperable and cannot provide surveillance of dispensing units to the attendant at the control station, and an emergency stop has not been approved by OSFM and provided in lieu of the camera as provided in this subsection (g), self-service dispensing of fuel at these dispensers is prohibited.
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Warning sign for dispenser 3 is falling off. Repair or replace. 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers”
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020250573 (Pending)    Issue Date: 3/5/2025    Expiration Date: 5/4/2025    View NOV Form

Tanks Violation
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site.
1, 2 Line interstitial sensors have been raised and rendered inoperational. - Dispenser 11/12 has a raised sensor. Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
Facility Miscellaneous - LP storage needs to be moved. It is blocking the overfill alarm and the emergency shut off switch. Ice cooler needs to be moved also. It is blocking an emergency shut off switch. The distance of any LP gas storage cabinet from any opening into any building, including any doorway or window, shall not be less than 5 feet, or in the event there is only one point of egress out of the building, shall not be less than 10 feet.
Facility Miscellaneous - The control station needs a emergency shut off sign. 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.
Facility Miscellaneous - The emergency shut off switch at the control station is blocked with alcohol. The display needs to be moved or move the emergency shut off switch.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site.
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
1, 2 Tank monitor does not appear to function properly and requires maintenance. - The ATG green and yellow indicator lights are out. Replace bulbs.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

No Forms Found