Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2041369
Status: Active
Facility Name: Speedway #1425
Address: 10250 Lemont Road Suite A Darien, IL 60439
County: Du Page
Property Parcel: 10-08-304-007
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA001830
Green Tag Issue Date: 6/25/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500 Springfield, OH 45501
Owner Status: Current Owner
Purchase Date: 5/13/2011
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/8/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner 5/13/2011
U0005658 Gas City, Ltd. Former Owner
U0030958 Prarie State Enterprises of Darien, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261967 (Pending)    Issue Date: 8/4/2026    Expiration Date: 10/3/2026    View NOV Form

Tanks Violations
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - 7-23-26 your testing contractor failed the sump sensors located in the STP's and dispensers. They are not programmed for positive shut-down and the identifications for those sensors are not identified properly when alarm is trigured in the tank monitor. Must re-identify.
1 Miscellaneous - Must submit to inspector the amount of the release from your reconsiliation when the dispenser was struck.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2026-0617 7/23/2026 Emergency Response

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/11/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/2005

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2026 4/8/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2026 4/8/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/23/2026 7/23/2027
Overfill Prev Device Overfill Drop Tube Valve 4/8/2026 4/8/2029
Piping Flexible Double Wall OPW Pisces Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown No passing test found No passing test found
Spill Contain Device Single Wall Spill Bucket 6/30/2024 6/30/2027
Tank Composite Double Wall Modern Welding Glasteel II Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 7/23/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/19/2011



Tank Number 2

Capacity: 7000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/11/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/2005

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2026 4/8/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2026 4/8/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/23/2026 7/23/2027
Overfill Prev Device Overfill Drop Tube Valve 4/8/2026 4/8/2029
Piping Flexible Double Wall OPW Pisces Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown No passing test found No passing test found
Spill Contain Device Single Wall Spill Bucket 6/30/2024 6/30/2027
Tank Composite Double Wall Modern Welding Glasteel II Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 7/23/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/19/2011



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/11/2004 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/2005

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2026 4/8/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2026 4/8/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/23/2026 7/23/2027
Overfill Prev Device Overfill Drop Tube Valve 4/8/2026 4/8/2029
Piping Flexible Double Wall OPW Pisces Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown No passing test found No passing test found
Spill Contain Device Double Wall Spill Bucket 4/9/2026 4/9/2029
Tank Composite Double Wall Modern Welding Glasteel II Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 7/23/2026
Tank Composite Double Wall Modern Welding Glasteel II Precision Test (Tank) Pass 12/8/2022
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/19/2011

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump No passing test found No passing test found
Leak Detect - Piping Sump Sensor with positive shutdown 7/23/2026 7/23/2027

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2041369 Speedway #1425 Darien 02/12/2026 Letter Form