Notice of Violations (Current)
NOV Number:
E0020261967
(Pending)
Issue Date:
8/4/2026
Expiration Date:
10/3/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - 7-23-26 your testing contractor failed the sump sensors located in the STP's and dispensers. They are not programmed for positive shut-down and the identifications for those sensors are not identified properly when alarm is trigured in the tank monitor. Must re-identify. |
| 1 |
Miscellaneous - Must submit to inspector the amount of the release from your reconsiliation when the dispenser was struck. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 2026-0617 |
7/23/2026 |
Emergency Response |
|
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/11/2004 |
|
Abandoned Material: |
|
| Current Age: |
21 |
|
Abandoned Date: |
|
| Install Date: |
1/1/2005 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/2005 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/8/2026 |
4/8/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
4/8/2026 |
4/8/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
7/23/2026 |
7/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/8/2026 |
4/8/2029 |
|
Piping
|
Flexible Double Wall OPW Pisces |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
No passing test found |
No passing test found |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
No passing test found |
No passing test found |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/30/2024 |
6/30/2027 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Pisces
|
Precision Test (Piping)
|
Pass
|
7/23/2026
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
5/19/2011
|
Tank Number 2
| Capacity: |
7000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/11/2004 |
|
Abandoned Material: |
|
| Current Age: |
21 |
|
Abandoned Date: |
|
| Install Date: |
1/1/2005 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/2005 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/8/2026 |
4/8/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
4/8/2026 |
4/8/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
7/23/2026 |
7/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/8/2026 |
4/8/2029 |
|
Piping
|
Flexible Double Wall OPW Pisces |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
No passing test found |
No passing test found |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
No passing test found |
No passing test found |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/30/2024 |
6/30/2027 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Pisces
|
Precision Test (Piping)
|
Pass
|
7/23/2026
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
5/19/2011
|
Tank Number 3
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/11/2004 |
|
Abandoned Material: |
|
| Current Age: |
21 |
|
Abandoned Date: |
|
| Install Date: |
1/1/2005 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/2005 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/8/2026 |
4/8/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
4/8/2026 |
4/8/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
7/23/2026 |
7/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/8/2026 |
4/8/2029 |
|
Piping
|
Flexible Double Wall OPW Pisces |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
No passing test found |
No passing test found |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
No passing test found |
No passing test found |
|
Spill Contain Device
|
Double Wall Spill Bucket |
4/9/2026 |
4/9/2029 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Pisces
|
Precision Test (Piping)
|
Pass
|
7/23/2026
|
|
Tank
|
Composite Double Wall Modern Welding Glasteel II
|
Precision Test (Tank)
|
Pass
|
12/8/2022
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
5/19/2011
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
2041369
|
Speedway #1425
|
Darien
|
02/12/2026
|
Letter
Form
|