Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2041114
Status: Active
Facility Name: Hiraba Food & Gas
Address: 2 East 159th Street Harvey, IL 60426
County: Cook
Property Parcel: 29-20-100-001-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001306
Green Tag Issue Date: 6/25/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Adarsh Partners, LLC
Owner Address: 2 East 159th Street Harvey, IL 60426
Owner Status: Current Owner
Purchase Date: 6/18/2013
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 9/24/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/25/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039095 Adarsh Partners, LLC Current Owner 6/18/2013
U0034963 Two East, Inc. Former Owner 7/15/2008
U0032847 JSS Enterprises Former Owner 9/1/2003
U0030504 Ahmad, Mohammad Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252615 (Pending)    Issue Date: 10/3/2025    Expiration Date: 12/2/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
1, 2 Annual leak detection certification not completed (Required annually). - ATG Cert. Past due 12/6/2024
1, 2 Line interstitial sensor functional test not accomplished (Required annually). - Past due 12/6/2024
1 Mechanical line leak detector requires annual functional test. - Past due 12/6/2024
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
1, 2 Tank interstitial sensor functional test not accomplished (Required annually). - Past due 12/6/2024

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/6/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/6/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/31/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/9/2025 10/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/9/2025 10/9/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/9/2025 10/9/2026
Overfill Prev Device Overfill Drop Tube Valve 4/19/2024 4/19/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/19/2024 4/19/2027
Leak Detect - Piping Sump Sensor 10/9/2025 10/9/2026
Spill Contain Device Single Wall Spill Bucket 4/19/2024 4/19/2027
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/9/2025



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/6/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/6/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/31/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/9/2025 10/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/9/2025 10/9/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/9/2025 10/9/2026
Overfill Prev Device Overfill Drop Tube Valve 4/19/2024 4/19/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 6/7/2024 6/7/2027
Leak Detect - Piping Sump Sensor 10/9/2025 10/9/2026
Spill Contain Device Single Wall Spill Bucket 4/19/2024 4/19/2027
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/9/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms