Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2040712
Status: Active
Facility Name: A.H. Petro Group , Inc.
Address: 6124 S. Ashland Avenue
Lessee
Chicago, IL 60636
County: Cook
Property Parcel: 20-18-423-055-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001401
Green Tag Issue Date: 1/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: T & R Properties, LLC
Owner Address: 6989 Fieldstone Drive
Burr Ridge, IL 60527
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 9/16/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/12/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035794 T & R Properties, LLC Current Owner
U0034458 S N S Food Mart, Inc. Former Owner 7/25/2007
U0030360 Ragat, Iran Former Owner 10/10/2001

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250207 (Pending)    Issue Date: 1/28/2025    Expiration Date: 3/29/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Line interstitial sensor functional test not accomplished (Required annually). - STP Sump Sensors
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - All C Operator Certificates are expired.
Facility Missing list of designated Class A/B & C Operators
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
3 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick.
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 8000 Gasoline - Premium Currently in use Federal $0.00
3 4000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
11/12 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms