Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0038988 |
LGP Realty Holdings, LP |
Current Owner |
5/19/2014 |
| U0037337 |
Lehigh Gas Wholesale Services Inc. |
Former Owner |
5/19/2014 |
| U0035189 |
PAV 2, LLC, |
Former Owner |
12/31/2012 |
| U0035024 |
Orchard Petroleum, LLC |
Former Owner |
9/29/2008 |
| U0000552 |
BP Products North America, Inc. |
Former Owner |
|
| U0027493 |
Amoco Oil Company |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020260885
(Pending)
Issue Date:
4/3/2026
Expiration Date:
6/2/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site. |
| 1, 2, 3, 4 |
Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site. |
| 1, 2, 3 |
Miscellaneous - Dispenser 11/12 UDC sump sensor wire is cracked. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site. |
| 1, 2, 3, 4 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All UDC sumps need triannual testing. Passing results shall be entered on OSFM portal. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/30/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
12/19/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/28/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
9/25/2025 |
9/25/2026 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
9/10/2026 |
9/10/2027 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
9/25/2025 |
9/25/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/22/2023 |
12/22/2026 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Galvanized Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
11/1/2024 |
11/1/2027 |
Leak Detect - Piping
|
Sump Sensor |
11/1/2024 |
11/1/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
10/16/2024 |
10/16/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
9/25/2025
|
|
Piping
|
Galvanized Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
11/6/2020
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/30/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
12/19/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/28/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
9/25/2025 |
9/25/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
9/25/2025 |
9/25/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/13/2023 |
11/13/2026 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Galvanized Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
11/1/2024 |
11/1/2027 |
Leak Detect - Piping
|
Sump Sensor |
11/1/2024 |
11/1/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
10/16/2024 |
10/16/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
9/25/2025
|
|
Piping
|
Galvanized Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
11/6/2020
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/30/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
12/19/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/28/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
9/25/2025 |
9/25/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
9/25/2025 |
9/25/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/13/2023 |
11/13/2026 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Galvanized Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
11/1/2024 |
11/1/2027 |
Leak Detect - Piping
|
Sump Sensor |
11/1/2024 |
11/1/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
10/16/2024 |
10/16/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
9/25/2025
|
|
Piping
|
Galvanized Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
11/6/2020
|
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
None |
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/30/2002 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
12/19/2001 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
3/28/2002 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
9/25/2025 |
9/25/2026 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
9/25/2025 |
9/25/2026 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/6/2023 |
11/6/2026 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
11/1/2024 |
11/1/2027 |
Leak Detect - Piping
|
Sump Sensor |
11/1/2024 |
11/1/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/16/2024 |
10/16/2027 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
9/25/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found