Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2040591
Status: Active
Facility Name: Highway Department Fueling Facility
Address: 16111 Nelson Road Woodstock, IL 60096
County: McHenry
Property Parcel:
Facility Type: County
Owner Type: County
Green Tag Decal: Y003958
Green Tag Issue Date: 5/17/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: County of McHenry
Owner Address: 2200 N. Seminary Ave. Woodstock, IL 60098
Owner Status: Current Owner
Purchase Date: 8/1/2001
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 8/31/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 5/17/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0009984 County of McHenry Current Owner 8/1/2001

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251795 (Pending)    Issue Date: 7/16/2025    Expiration Date: 9/14/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch
Facility Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly.

NOV Number: E0020251796 (Pending)    Issue Date: 7/16/2025    Expiration Date: 9/14/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/7/2001 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 8/2/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/24/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/21/2025 7/21/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/21/2025 7/21/2026
Overfill Prev Device Overfill Alarm 7/21/2025 7/21/2028
Overfill Prev Device Overfill Drop Tube Valve 7/21/2025 7/21/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/21/2025 7/21/2028
Leak Detect - Piping Sump Sensor 7/21/2025 7/21/2026
Spill Contain Device Double Wall Spill Bucket 7/21/2025 7/21/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/21/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/9/2024



Tank Number 2

Capacity: 5000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/7/2001 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 8/2/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/24/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/21/2025 7/21/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/21/2025 7/21/2026
Overfill Prev Device Overfill Alarm 7/21/2025 7/21/2028
Overfill Prev Device Overfill Drop Tube Valve 7/21/2025 7/21/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/21/2025 7/21/2028
Leak Detect - Piping Sump Sensor 7/21/2025 7/21/2026
Spill Contain Device Double Wall Spill Bucket 7/21/2025 7/21/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/21/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/9/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found