Notice of Violatlions (Current)
NOV Number:
E0020252258
(Pending)
Issue Date:
8/28/2025
Expiration Date:
10/27/2025
View NOV Form
Tanks |
Violations |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020252259
(Pending)
Issue Date:
8/28/2025
Expiration Date:
10/27/2025
View NOV Form
Tanks |
Violations |
1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose. |
Facility |
Miscellaneous - Both Emergency shut off switches require signs.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
1, 2 |
Miscellaneous - Under dispenser sump sensors are not shown on ATG. |