Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2040555
Status: Active
Facility Name: CYPR Harvey, Inc. d/b/a Quick Gas & Mini Mart, Inc.
Address: 15355 Dixie Highway
Harvey, IL 60426
County: Cook
Property Parcel: 29-18-111-024-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001849
Green Tag Issue Date: 12/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Harvey Real Estate, Inc.
Owner Address: 15355 Dixie Highway
Harvey, IL 60426
Owner Status: Current Owner
Purchase Date: 9/27/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/15/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040059 Harvey Real Estate, Inc. Current Owner 9/27/2018
U0030188 GID DEV Former Owner 4/1/2001
U0032561 Yafai, Nasser Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251114 (Pending)    Issue Date: 4/25/2025    Expiration Date: 6/24/2025    View NOV Form

Tanks Violation
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o)
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)
Facility Miscellaneous - LP Gas Storage tank cabinet is to close to opening of building.

NOV Number: E0020251116 (Pending)    Issue Date: 4/25/2025    Expiration Date: 6/24/2025    View NOV Form

Tanks Violation
4, 5 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Containment shall have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. 175.410 a) (Premium and Regular STP lids need repair/replace. Cracked.)
Facility Facility Operation and Maintenance Plan not completed or available. - Need to completely fill out.
Facility Miscellaneous - Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) (Inside E-stop)
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov.
Facility Missing list of designated Class A/B & C Operators - Form can be found at https://sfm.illinois.gov to download and complete.
4, 5, 6 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status)
4, 5, 6 Piping interstitial must be open in all sumps - Product piping test boots shall be pulled back after testing to allow the interstice to be open to the sump sensors 175.420 b) (Or Shrader valves need to be removed) (All STP's)
4, 5, 6 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (CSLD Tapes)
4, 5 Shear valve(s) not properly mounted and/or not at proper height. - All shear valves are required to be mounted. One or more shear valves in the above listed dispenser is not appropriately anchored.
4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5, 6 Tank precision test required. - Due to missing monthly CSLD Tapes

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
01-1264 7/19/2001 Removal Log 01266-2001REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 7/19/2001
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 7/19/2001
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 7/19/2001
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/6/2002 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 7/25/2002 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 10/1/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/3/2024 12/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD 12/3/2024 12/3/2025
Overfill Prev Device Overfill Drop Tube Valve 11/13/2023 11/13/2026
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2023 11/13/2026
Leak Detect - Piping Sump Sensor 12/3/2024 12/3/2025
Spill Contain Device Single Wall Spill Bucket 11/13/2023 11/13/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/3/2024



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/6/2002 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 7/25/2002 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 10/1/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/3/2024 12/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD 12/3/2024 12/3/2025
Overfill Prev Device Overfill Drop Tube Valve 11/13/2023 11/13/2026
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2023 11/13/2026
Leak Detect - Piping Sump Sensor 12/3/2024 12/3/2025
Spill Contain Device Single Wall Spill Bucket 11/13/2023 11/13/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/3/2024



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/6/2002 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 7/25/2002 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 10/1/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/3/2024 12/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD 12/3/2024 12/3/2025
Overfill Prev Device Overfill Drop Tube Valve 11/13/2023 11/13/2026
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 11/13/2023 11/13/2026
Leak Detect - Piping Sump Sensor 12/3/2024 12/3/2025
Spill Contain Device Single Wall Spill Bucket 11/13/2023 11/13/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 12/3/2024



Tank Number 7

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 7/19/2001
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 7/19/2001
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found