Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2040463
Status: Active
Facility Name: Circle K #6827
Address: 1127 North Eola Road
Aurora, IL 60504
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002817
Green Tag Issue Date: 2/7/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 11/7/2011
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/7/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 11/7/2011
U0033589 Jewel Food Stores, Inc. Former Owner
U0028677 Albertson's, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250725 (Pending)    Issue Date: 3/19/2025    Expiration Date: 5/18/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020250726 (Pending)    Issue Date: 3/19/2025    Expiration Date: 5/18/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Top steel lid rim support is deteriorated and broken. This needs to be repaired or replaced so lid does not fall into sump.
1, 2 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
Facility Miscellaneous - Emergency shut off switch at control station needs a sign install. 175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be conspicuously marked and readily accessible to the attendant, whether or not the control station is less than 20 feet from any dispenser or a security booth is provided for the attendant. The emergency stop shall be located in a position to allow all dispensing devices to be readily visible to the attendant, or as approved by OSFM. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Gasoline Does Not Exist Federal

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

No Forms Found