Notice of Violations (Current)
NOV Number:
E0020251366
(Pending)
Issue Date:
5/28/2025
Expiration Date:
7/27/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |
NOV Number:
E0020251367
(Pending)
Issue Date:
5/28/2025
Expiration Date:
7/27/2025
View NOV Form
Tanks |
Violation |
2 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed. SPECIFICALLY TANK 2, REGULAR UNLEADED NORTH TANK, WILL ALSO NEED TO REMOVE LIQUID FROM STP AND MAKE WATER TIGHT. |
1, 2, 3, 4 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Line leak detection equipment in alarm on ATG; Repair/replace as necessary to clear alarm. SPECIFICALLY L 3: FUEL ALARM (DISP 5-6), AND L 11: FUEL ALARM (DIESEL DISP). |
2 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - STP sump(s) contain(s) liquid, and has raised sensor. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor(s) as necessary. |