Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2040391
Status: Active
Facility Name: Lucky Gasoline, Inc.
Address: 1469 S. Randall Road
Algonquin, IL 60102
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001692
Green Tag Issue Date: 5/2/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Lucky Real Properties, LLC
Owner Address: 1469 S. Randall Rd.
Algonquin, IL 60102
Owner Status: Current Owner
Purchase Date: 7/13/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/31/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/2/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039313 Lucky Real Properties, LLC Current Owner 7/13/2018
U0035136 Algonquin Gasoline, Inc. Former Owner 12/8/2008
U0000552 BP Products North America, Inc. Former Owner
U0023834 BP Amoco Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251366 (Pending)    Issue Date: 5/28/2025    Expiration Date: 7/27/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

NOV Number: E0020251367 (Pending)    Issue Date: 5/28/2025    Expiration Date: 7/27/2025    View NOV Form

Tanks Violation
2 Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed. SPECIFICALLY TANK 2, REGULAR UNLEADED NORTH TANK, WILL ALSO NEED TO REMOVE LIQUID FROM STP AND MAKE WATER TIGHT.
1, 2, 3, 4 Line leak detection equipment in alarm or failed test, must repair or replace. - Line leak detection equipment in alarm on ATG; Repair/replace as necessary to clear alarm. SPECIFICALLY L 3: FUEL ALARM (DISP 5-6), AND L 11: FUEL ALARM (DIESEL DISP).
2 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - STP sump(s) contain(s) liquid, and has raised sensor. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor(s) as necessary.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/14/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 4/1/2025 4/1/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/22/2023 3/22/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 4/1/2024 4/1/2027
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 4/1/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/14/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 4/1/2025 4/1/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/22/2023 3/22/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 4/1/2024 4/1/2027
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 4/1/2025



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/14/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 4/1/2025 4/1/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/22/2023 3/22/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 4/1/2024 4/1/2027
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 4/1/2025



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/3/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/14/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/13/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 4/1/2025 4/1/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/22/2023 3/22/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 4/1/2024 4/1/2027
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 4/1/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 21/22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/1/2024 4/1/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026

MFD Motorfuel Dispensing Forms

No Forms Found