Notice of Violations (Current)
NOV Number:
E0020260729
(Pending)
Issue Date:
3/12/2026
Expiration Date:
5/11/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Financial responsibility must be reported yearly |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| 1 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
NOV Number:
E0020260730
(Pending)
Issue Date:
3/12/2026
Expiration Date:
5/11/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Fire Extinguishers - Past due for annual testing |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/5/2000 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
2/16/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/17/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/10/2025 |
6/10/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 with CSLD |
6/10/2025 |
6/10/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/18/2026 |
6/18/2029 |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/4/2024 |
4/4/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
4/4/2024
|
Tank Number 2
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/5/2000 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
2/16/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/17/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/10/2025 |
6/10/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 with CSLD |
6/10/2025 |
6/10/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/24/2024 |
7/24/2027 |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/24/2024 |
7/24/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
4/4/2024
|
Tank Number 3
| Capacity: |
5000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/5/2000 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
2/16/2000 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
2/17/2000 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/10/2025 |
6/10/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 with CSLD |
6/10/2025 |
6/10/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/24/2024 |
7/24/2027 |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/24/2024 |
7/24/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
4/4/2024
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found