1, 4 |
Annual leak detection certification not completed (Required annually). - ATG Failed.
"Premium probe FAILS, upon arrival Premium was reading 1.15" of water, per stick read at Atg no water just sediment. When testing probe for alarms set waters to read 0" outside of tank and probe was reading 1.15" needs to be fixed/replaced."
"Diesel INT sensor FAILS due to bad wiring from tank monitor to sensor & maybe sensor, at arrival & departure DSL INT sensor reads low liquid alarm & when set to read normal or high liquid alarm sensor reads low liquid alarm. Disconnected wires at splice in junction box & sensor still reads low liquid alarm; wiring needs to be fixed. Junction box was taken apart at arrival exposing wire splice. Put box back on but box is missing screw to keep it sealed; needs to be fixed." |