Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2039646
Status: Active
Facility Name: Circle K #6753
Address: 1190 US Highway 34
Oswego, IL 60543
County: Kendall
Property Parcel: 03-02-450-003
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003360
Green Tag Issue Date: 11/22/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0028798 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250091 (Pending)    Issue Date: 1/13/2025    Expiration Date: 3/14/2025    View NOV Form

Tanks Violation
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - 175.210 g) All dispensing units shall be readily visible from the control station without assistive devices. However, as an alternative, in the event that the attendant's view of a dispenser is permanently obstructed, or if a dispenser is located so that activity at the dispenser is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. The cameras shall be allowed to sweep to provide a view of multiple dispensing locations, but must provide a view on the screen of each dispensing unit at least every 30 seconds. In lieu of the closed-circuit camera, the facility may elect to have an emergency stop that shall be located at least 20 and not more than 50 feet from the dispenser that has a permanently obstructed view. Using an emergency stop in lieu of the closedcircuit camera pursuant to this subsection (g) must be approved in advance by OSFM. If a closed-circuit camera or viewing screen is inoperable and cannot provide surveillance of dispensing units to the attendant at the control station, and an emergency stop has not been approved by OSFM and provided in lieu of the camera as provided in this subsection (g), self-service dispensing of fuel at these dispensers is prohibited.

NOV Number: E0020250094 (Pending)    Issue Date: 1/13/2025    Expiration Date: 3/14/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The steel lid support is not secured in the concrete. It comes out with the lid.
1, 2 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
Facility Facility Operation and Maintenance Plan not completed or available. - Update 0&M
1, 2 Line interstitial sensors have been raised and rendered inoperational. - UDC sumps need sensors lowered. T2 STP sump sensor is lying on bottom of sump.Sensor needs to be stood up. 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Update Emergency Procedure Plan
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active

MFD Motorfuel Dispensing Forms

No Forms Found