Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2039549
Status: Active
Facility Name: Midwest Convenience, Inc.
Address: 1300 Normantown Road Romeoville, IL 60446
County: Will
Property Parcel: 12-02-31-200-017-000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002869
Green Tag Issue Date: 12/14/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Anabi Real Estate Development, LLC, Designated Series JJ
Owner Address: 1450 N. Benson Avenue, Suite A Upland, CA 91786
Owner Status: Current Owner
Purchase Date: 8/10/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/10/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/14/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040350 Anabi Real Estate Development, LLC, Designated Series JJ Current Owner 8/10/2021
U0026552 Speedway, LLC Former Owner 5/13/2011
U0005658 Gas City, Ltd. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252040 (Pending)    Issue Date: 8/12/2025    Expiration Date: 10/11/2025    View NOV Form

Tanks Violations
5 Line leak detection equipment in alarm or failed test, must repair or replace. - Line leak detection in alarm.
5 Precision tank test required. - No recods for ATG testing available.
5 Submit Notification Form For Tank Status Change - Submit notification form for when the tank went out of service. Form can be found at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.
1 Triennial spill prevention equipment testing not completed. - North spill bucket for tank 1 needs to be tested. Laast tested 10/6/2021.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/18/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/13/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/8/2025 4/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/8/2025 4/8/2026
Overfill Prev Device Overfill Drop Tube Valve 6/9/2023 6/9/2026
Overfill Prev Device Overfill Drop Tube Valve 5/17/2023 5/17/2026
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026
Spill Contain Device Double Wall Spill Bucket 10/1/2024 10/1/2027
Spill Contain Device Single Wall Spill Bucket 10/6/2021 10/6/2024
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 5/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/27/2011
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/27/2011



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/18/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/13/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/8/2025 4/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/8/2025 4/8/2026
Overfill Prev Device Overfill Drop Tube Valve 6/9/2023 6/9/2026
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 5/6/2022 5/6/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026
Spill Contain Device Single Wall Spill Bucket 10/1/2024 10/1/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 5/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/27/2011
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/27/2011



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/18/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/13/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/8/2025 4/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/8/2025 4/8/2026
Overfill Prev Device Overfill Drop Tube Valve 12/31/2024 12/31/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026
Spill Contain Device Double Wall Spill Bucket 12/31/2024 12/31/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 5/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/27/2011
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/27/2011



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/16/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/13/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/8/2025 4/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/8/2025 4/8/2026
Overfill Prev Device Overfill Drop Tube Valve 12/31/2024 12/31/2027
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026
Spill Contain Device Double Wall Spill Bucket 12/31/2024 12/31/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 5/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/27/2011
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/27/2011



Tank Number 5

Capacity: 2000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/18/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/13/2000 Red Tag Issue Date: 7/28/2022
Last Used Date: 7/28/2022 Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/6/2022 5/6/2023
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/6/2022 5/6/2023
Overfill Prev Device Overfill Drop Tube Valve 5/13/2020 5/13/2023
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 5/6/2022 5/6/2023
Spill Contain Device Single Wall Spill Bucket 4/26/2024 4/26/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/27/2011
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/27/2011



Tank Number 6

Capacity: 2000 Petroleum Use:
Product: Racing Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/18/2000 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 7/13/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/8/2025 4/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/8/2025 4/8/2026
Overfill Prev Device Overfill Drop Tube Valve 5/17/2023 5/17/2026
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026
Spill Contain Device Single Wall Spill Bucket 4/26/2024 4/26/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 5/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/27/2011
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/27/2011

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 20/21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 4/8/2025 4/8/2026

MFD Motorfuel Dispensing Forms

No Forms Found