Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2037331
Status: Active
Facility Name: Thorek Hospital & Medical Center
Address: 850 W Irving Park Road
Chicago, IL 60613
County: Cook
Property Parcel:
Facility Type: Hospital
Owner Type: Private
Green Tag Decal: Y003569
Green Tag Issue Date: 10/6/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Thorek Hospital & Medical Center
Owner Address: 850 W Irving Park Road
Chicago, IL 60613
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/14/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0027554 Thorek Hospital & Medical Center Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/27/1998 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 5/17/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/17/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 3/18/2025 3/18/2026
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/18/2025 3/18/2026
Leak Detect - Piping American with Annual Prec Line Testing Suction 4/17/2017 4/17/2018
Leak Detect - Tank Automatic Tank Gauging EBW Auto-Stik Jr. 3/18/2025 3/18/2026
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/18/2025 3/18/2028
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 3/18/2025
Piping Steel Single Wall Piping Precision Test (Piping) Pass 3/18/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 11/21/2019



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found