Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2037231
Status: Active
Facility Name: Y & A Fuel, Inc d/b/a Aurora Amoco
Address: 2112 Ogden Avenue Aurora, IL 60504
County: Kane
Property Parcel: 15-36-421-010
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000197
Green Tag Issue Date: 10/7/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: K B Properties of Illinois, LLC
Owner Address: 2124 Ogden Avenue, Suite 304 Aurora, IL 60504
Owner Status: Current Owner
Purchase Date: 1/31/2019
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 6/8/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040419 K B Properties of Illinois, LLC Current Owner 1/31/2019
U0027402 Kishore Belani Khemani, Inc. Former Owner 4/21/1999

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261819 (Pending)    Issue Date: 7/15/2026    Expiration Date: 9/13/2026    View NOV Form

Tanks Violations
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The regular STP sump lid is broken and needs to be replaced.
1 Miscellaneous - Probe cap is off. STP sump is filled with water to top of probe drop tube.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/7/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 4/22/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/28/1999

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/14/2023 8/14/2026
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/8/2025 10/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/8/2025 10/8/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve Not applicable Not applicable
Overfill Prev Device Overfill Drop Tube Valve 10/8/2025 10/8/2028
Piping Flexible Double Wall Total Containment Omniflex I Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 10/8/2025 10/8/2028
Tank Composite Double Wall Permatank Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 10/8/2025
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 7/12/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/21/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 4/22/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/28/1999

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/14/2023 8/14/2026
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/8/2025 10/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/8/2025 10/8/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve Not applicable Not applicable
Overfill Prev Device Overfill Drop Tube Valve 10/8/2025 10/8/2028
Piping Flexible Double Wall Total Containment Omniflex I Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 10/8/2025 10/8/2028
Tank Composite Double Wall Permatank Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 10/8/2025
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 7/12/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found