Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2037166
Status: Active
Facility Name: Elgin Convenience 1
Address: 1190 N. McLean Blvd. Elgin, IL 601231723
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001452
Green Tag Issue Date: 5/22/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: RPT Enterprises, LLC
Owner Address: 475 Supreme Drive Bensenville, IL 60106
Owner Status: Current Owner
Purchase Date: 2/1/2016
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 2/12/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/22/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038287 RPT Enterprises, LLC Current Owner 2/1/2016
U0027821 Three Brothers Petroleum, Inc. Former Owner 3/15/1999
U0027331 North Mclean Citgo LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252108 (Pending)    Issue Date: 8/14/2025    Expiration Date: 10/13/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
1, 2, 3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
1, 2, 3 Annual line precision and mechanical line leak detector functional test not completed. - Annual third-party precision line and leak detector test is required.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/12/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 9/22/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/22/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/18/2025 8/18/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/18/2025 8/18/2026
Overfill Prev Device Overfill Drop Tube Valve 5/18/2023 5/18/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 5/18/2023 5/18/2026
Leak Detect - Piping Sump Sensor 8/18/2025 8/18/2026
Spill Contain Device Single Wall Spill Bucket 5/18/2023 5/18/2026
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 8/18/2025
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 5/15/2024



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/12/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 9/22/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/22/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/18/2025 8/18/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/18/2025 8/18/2026
Overfill Prev Device Overfill Drop Tube Valve 5/18/2023 5/18/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 5/18/2023 5/18/2026
Leak Detect - Piping Sump Sensor 8/18/2025 8/18/2026
Spill Contain Device Single Wall Spill Bucket 5/18/2023 5/18/2026
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 8/18/2025
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 5/15/2024



Tank Number 3

Capacity: 15000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/12/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 9/22/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/22/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/18/2025 8/18/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/18/2025 8/18/2026
Overfill Prev Device Overfill Drop Tube Valve 5/18/2023 5/18/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 5/18/2023 5/18/2026
Leak Detect - Piping Sump Sensor 8/18/2025 8/18/2026
Spill Contain Device Single Wall Spill Bucket 5/18/2023 5/18/2026
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 8/18/2025
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 5/15/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found