Notice of Violatlions (Current)
NOV Number:
E0020252765
(Pending)
Issue Date:
10/20/2025
Expiration Date:
12/19/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020252774
(Pending)
Issue Date:
10/20/2025
Expiration Date:
12/19/2025
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - The main hose has a tear in it. Replace |
| Facility |
Miscellaneous - The emergency shut off switch at the control station is blocked and needs a sign. Either remove product display or relocate the shut off switch. A sign will be required also.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |