Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2036541
Status: Active
Facility Name: Woodward BP
Address: 1935 87th Street (Boughton Rd.)
Woodridge, IL 60565
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001197
Green Tag Issue Date: 6/12/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Sumon Saha
Owner Address: 1935 Boughton Rd.
Woodridge, IL 605174952
Owner Status: Current Owner
Purchase Date: 12/23/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/10/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/12/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038658 Saha, Sumon Current Owner 12/23/2016
U0035690 Professional Petroleum Marketing Group, Inc. (PPMG) Former Owner 8/16/2009
U0035189 PAV 2, LLC, Former Owner 6/15/2009
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250529 (Pending)    Issue Date: 2/26/2025    Expiration Date: 4/27/2025    View NOV Form

Tanks Violation
Facility Financial responsibility must be reported yearly
1, 2 Line leak detection equipment in alarm or failed test, must repair or replace. - Disp 5/6 sensor fails. Sensor does not go into alarm when put into alarm status. Sensor needs to be replaced SITE WILL NEED TO BE SET UP FOR POSITIVE SHUTDOWN.
2 Line leak detection equipment in alarm or failed test, must repair or replace. - Regular 2” STP Sump sensor fails. Sump sensor will not clear after being put in alarm. Sensor in alarm upon departure
3 Line leak detection equipment in alarm or failed test, must repair or replace. - Disp 5/6 sensor fails. Sensor does not go into alarm when put into alarm status. Sensor needs to be replaced SITE WILL NEED TO BE SET UP FOR POSITIVE SHUTDOWN.
1 Tank interstitial sensors in alarm or failed test, must repair or replace. - Regular 1” Brine INT sensor fails. Sensor in alarm upon contractor completion. Sensor bounces in between high-Low liquid alarm.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms