Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2036185
Status: Active
Facility Name: Streamwood Behavioral Healthcare System
Address: 1400 E. Irving Park Rd.
Streamwood, IL 60107
County: Cook
Property Parcel: 06-25-400-012-0000
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: X004480
Green Tag Issue Date: 5/10/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Streamwood Behavioral Healthcare Sysem
Owner Address: 1400 East Irving Park Rd.
Streamwood, IL 60107
Owner Status: Current Owner
Purchase Date: 11/15/2010
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/6/2024

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038281 Streamwood Behavioral Healthcare Sysem Current Owner 11/15/2010
U0033742 PSI Solutions Former Owner 6/1/2005
U0032739 Ardent Health Former Owner
U0028046 Behavior Health Center Former Owner
U0003283 Community Psychiatric Ctr Former Owner
U0003283 Community Psychiatric Ctr Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240841 (Pending)    Issue Date: 3/21/2024    Expiration Date: 5/20/2024    View NOV Form

Tanks Deficiency
1 Precision tank test required. - Perform due to ingress of water into the tank

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 1100 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/21/1998 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/24/2021 8/24/2024
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/17/2023 11/17/2024
Overfill Prev Device Overfill Drop Tube Valve 8/12/2021 8/12/2024
Piping Flexible Double Wall A.P.T. Poly Tech P100SC N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech P100SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/12/2021 8/12/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/27/2024

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found