Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2035697
Status: Active
Facility Name: 7-Eleven #32202
Address: 1202 North Eola Aurora, IL 60514
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000112
Green Tag Issue Date: 3/25/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: 7-Eleven, Inc.
Owner Address: 3200 Hackberry Road - Gas Compliance Irving, TX 75063
Owner Status: Current Owner
Purchase Date: 1/1/1997
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/8/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0014207 7-Eleven, Inc. Current Owner 1/1/1997
U0014208 Southland Corp Former Owner 1/1/1997
U0023040 7-Eleven, Inc./DO NOT USE # Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020262083 (Pending)    Issue Date: 8/18/2026    Expiration Date: 10/17/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - I can see a intercom system, but it's blocked by display racks. I don't know if it is functional. 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.
Facility Miscellaneous - Control station does not have a readily accessible emergency shut off switch. A sign is required also as stated in the remarks.

NOV Number: E0020262084 (Pending)    Issue Date: 8/18/2026    Expiration Date: 10/17/2026    View NOV Form

Tanks Violations
1, 3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The regular and diesel probe well steel lids are not secured. The steel frame comes up from the concrete. The lid supporting brackets and lids need to be secured.
1, 2 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose it is kinked.
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - Dispenser sumps 5/6, 9/10, and STP sumps T1 regular and T3 diesel have raised sensors. Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
2 Miscellaneous - Tank annular sensor wire is open into the tank interstice.
1, 2, 3 Piping interstitial must be open in all sumps - Check all UDC and STP sumps to make sure interstice is able to drain into sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00


Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active


MFD Motorfuel Dispensing Forms

No Forms Found