| 1, 3 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - The regular and diesel probe well steel lids are not secured. The steel frame comes up from the concrete. The lid supporting brackets and lids need to be secured. |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose it is kinked. |
| 1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser sumps 5/6, 9/10, and STP sumps T1 regular and T3 diesel have raised sensors.
Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid
per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 2 |
Miscellaneous - Tank annular sensor wire is open into the tank interstice. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - Check all UDC and STP sumps to make sure interstice is able to drain into sumps. |