Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2035598
Status: Active
Facility Name: Halsted 844, Inc. d/b/a Midwest Gas
Address: 844 S. Halsted
Chicago Heights, IL 60411
County: Cook
Property Parcel: 32-17-424-008-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002040
Green Tag Issue Date: 1/8/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: HPG Holding, Inc.
Owner Address: 12346 S. Keeler Ave.
Alsip, IL 60803
Owner Status: Current Owner
Purchase Date: 3/5/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/9/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/8/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039315 HPG Holding, Inc. Current Owner 3/5/2021
U0040108 Chicago Title Land Trust Co. Trust #11557 Former Owner 3/6/2018
U0027952 Ali, Akhtar Former Owner 12/10/1998
U0025636 Ali Akhtar Former Owner 3/10/1995
U0025636 Ali Akhtar Former Owner 3/10/1995
U0025636 Ali Akhtar Former Owner 3/10/1995
U0038057 Khan, Atlas Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250357 (Pending)    Issue Date: 2/11/2025    Expiration Date: 4/12/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)

NOV Number: E0020250358 (Pending)    Issue Date: 2/11/2025    Expiration Date: 4/12/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Perform test, complete form (form is available at https://sfm.illinois.gov) and maintain on site with other annual testing documentation.
4, 5 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed. Testing shall be completed and submitted to OSFM.
4, 5 Mechanical line leak detector requires annual functional test.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - Primary A / B certified operator shall be retrained as a result of NOV being issued. (Ahemd Moctar)
4, 5 Precision line test required. - Annual Precision line test past due.
4, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5 Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green and Yellow)

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-1221 5/20/1999 Removal Log 00224-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-1221 Eligible 5/1/2000 5/10/2000 $100,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 7500 Gasoline Removed Federal $0.00 05/20/1999 - REM
2 7500 Gasoline Removed Federal $0.00 05/20/1999 - REM
3 7500 Gasoline Removed Federal $0.00 05/20/1999 - REM
4 10000 Gasoline - Regular Currently in use Federal $0.00
5 6000 Gasoline - Premium Currently in use Federal $0.00
6 10000 Diesel Fuel Does Not Exist Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found