Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Perform test, complete form (form is available at https://sfm.illinois.gov) and maintain on site with other annual testing documentation. |
4, 5 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed. Testing shall be completed and submitted to OSFM. |
4, 5 |
Mechanical line leak detector requires annual functional test. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site. |
Facility |
Missing copies of current testing certificates for operator training - Primary A / B certified operator shall be retrained as a result of NOV being issued. (Ahemd Moctar) |
4, 5 |
Precision line test required. - Annual Precision line test past due. |
4, 5 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form. |
4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
4, 5 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green and Yellow) |