Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2035300
Status: Active
Facility Name: Shree Sudarsan BP, Inc.
Address: 2791 West Ogden Avenue
Oswego, IL 60543
County: Kendall
Property Parcel: 03-10-304-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003381
Green Tag Issue Date: 1/4/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Shree Sudarsan BP, Inc.
Owner Address: 2791 US Route 34
Oswego, IL 60446
Owner Status: Current Owner
Purchase Date: 5/26/2015
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 9/3/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037856 Shree Sudarsan BP, Inc. Current Owner 5/26/2015
U0035189 PAV 2, LLC, Former Owner 12/5/2013
U0034435 Oswego Petroleum, LLC Former Owner 10/9/2007
U0000574 Amoco Oil Company Former Owner 10/25/1996
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251060 (Pending)    Issue Date: 4/17/2025    Expiration Date: 6/16/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
1 Miscellaneous - Vapor cap is missing.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
1, 2, 3 Piping containment sump failed triennial testing. Repair or replace. - Dispenser 1/2 sump failed. Repair sump and retest. Passing results shall be entered on OSFM portal.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
2, 3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP sumps need triannual testing. Passing results shall be entered on OSFM portal.

NOV Number: E0020251061 (Pending)    Issue Date: 4/17/2025    Expiration Date: 6/16/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms