Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2035104
Status: Active
Facility Name: Naperville and Food, Inc. (BP)
Address: 4940 South Route 59 Naperville, IL 60540
County: Du Page
Property Parcel: 07-01-15-302-115-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001701
Green Tag Issue Date: 1/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: NW Services LLC
Owner Address:
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 11/15/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/10/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036307 NW Services LLC Current Owner
U0035189 PAV 2, LLC, Former Owner 6/18/2009
U0000574 Amoco Oil Company Former Owner 4/10/1997
U0000552 BP Products North America, Inc. Former Owner
U0028366 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251490 (Pending)    Issue Date: 6/10/2025    Expiration Date: 8/9/2025    View NOV Form

Tanks Violations
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - Dispenser Containment has fuel within setting off the interstital sensor Must repair leak
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill buckets

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use: None
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/12/2000 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 10/1/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/1/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/4/2024 12/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/4/2024 12/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/4/2024 12/4/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/9/2022 12/9/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025
Spill Contain Device Single Wall Spill Bucket 11/21/2022 11/21/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use: None
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/12/2000 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 10/1/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/1/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/4/2024 12/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/4/2024 12/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/4/2024 12/4/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/9/2022 12/9/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025
Spill Contain Device Single Wall Spill Bucket 11/21/2022 11/21/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use: None
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/12/2000 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 10/1/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/1/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/4/2024 12/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/4/2024 12/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/4/2024 12/4/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/9/2022 12/9/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025
Spill Contain Device Single Wall Spill Bucket 11/21/2022 11/21/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 11/21/2022
Tank Fiberglass Double Wall Precision Test (Tank) Pass 11/21/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025



Name\ID 11/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2022 11/21/2025
Leak Detect - Piping Sump Sensor 12/4/2024 12/4/2025

MFD Motorfuel Dispensing Forms