| 2 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - T2 regular north STP sump lid needs to be repaired and or replaced so it can be opened. The handle is broken and it is wedged into the supporting rim. |
| 1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 7/8 and T1 STP sump has a raised sensor. Lower sensors. Dispenser 5/6 and T2 has sensors lying down. Sensors shall be stood up. |
| Facility |
Miscellaneous - There is product in dispenser 7/8. The product needs to be removed. |
| 1 |
Miscellaneous - ATG is reading 47 gallons .82" of water in tank. |
| 1, 2, 3 |
Precision line test required. - Multiple times throughout the last 2 years different sensors have been in alarm. At this time two of the sensors have been raised and there is product in dispenser 7/8. A precision line test is needed to confirm there is no line leaks. |
| 2 |
Tank interstitial sensors in alarm or failed test, must repair or replace. - ATG is in alarm L5 High Liquid Alarm. It has been in alarm multiple times over the last 2 years. This shall be repaired so ATG is clear of alarms. |