Notice of Violations (Current)
NOV Number:
E0020261623
(Pending)
Issue Date:
6/24/2026
Expiration Date:
8/23/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Dispenser 7/8 Intercom is not functioning.
175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020261624
(Pending)
Issue Date:
6/24/2026
Expiration Date:
8/23/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose |
| 1, 2 |
Line interstitial sensors have been raised and rendered inoperational. - Sensors are raised in STP sumps.
Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid
per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 2 |
Miscellaneous - ATG is in alarm. L4 Fuel Alarm. |
| 2 |
Miscellaneous - ATG shows 4 gallons .79" of water in tank. |
| 2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |