Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2034817
Status: Active
Facility Name: Bucky's Express #6533
Address: 1290 So. Route 59
Naperville, IL 60566
County: Du Page
Property Parcel: 07-27-108-003
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001728
Green Tag Issue Date: 4/7/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave.
P.O. Box 3004
Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 5/14/2021
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/27/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 5/14/2021
U0036012 Buchanan Energy (S), LLC Former Owner 12/9/2010
U0010471 Exxon Mobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01506-2024UPG Upgrade Approved / Amended 11/21/2024 11/21/2024 5/21/2025 Documents
00426-2025UPG Upgrade Approved / Issued 4/8/2025 4/8/2025 10/8/2025 Documents
01638-2024REM Removal Approved / Issued 12/19/2024 12/19/2024 6/20/2025 Documents

Notice of Violations (Current)

NOV Number: E0020251040 (Pending)    Issue Date: 4/16/2025    Expiration Date: 6/15/2025    View NOV Form

Tanks Violation
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing list of designated Class A/B & C Operators
1, 2 Tank interstitial sensors in alarm or failed test, must repair or replace. - Per the testing contractor these two tanks had the wrong interstitial sensors sent with the new tank monitor and are not compatible
1, 2 Triennial spill prevention equipment testing not completed. - Spill buckets
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All dispensers
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP's
2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All dispensers
2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP's

NOV Number: E0020251041 (Pending)    Issue Date: 4/16/2025    Expiration Date: 6/15/2025    View NOV Form

Tanks Violation
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Signs are not visible from the most West dispensers on each row.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/16/1996 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 6/5/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/19/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 600 4/8/2025 4/8/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 1/10/2024 1/10/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 4/8/2025 4/8/2028
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 1/22/2025 1/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026
Spill Contain Device Double Wall Spill Bucket 1/22/2025 1/22/2028
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 1/13/2023
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 4/8/2025
Tank Fiberglass Brine Filled Double Wall Precision Test (Tank) Pass 4/8/2025



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/16/1996 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 6/5/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/19/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2025 4/8/2026
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 600 4/8/2025 4/8/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 1/10/2024 1/10/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 4/8/2025 4/8/2028
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 1/22/2025 1/22/2028
Spill Contain Device Double Wall Spill Bucket 1/22/2025 1/22/2028
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 1/13/2023
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 4/8/2025
Tank Fiberglass Brine Filled Double Wall Precision Test (Tank) Pass 4/8/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2025 1/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2025 4/8/2026

MFD Motorfuel Dispensing Forms