Notice of Violatlions (Current)
NOV Number:
E0020251892
(Pending)
Issue Date:
7/28/2025
Expiration Date:
9/26/2025
View NOV Form
Tanks |
Violations |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
Facility |
LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Section 175.210 q) Collision Protection and Setbacks for LP Gas Storage Cabinets at Motor Fuel
Dispensing Facilities.
1) LP gas storage cabinets (including cabinets for LP gas tank exchange for
gas grills) shall comply with Section 8.4 of NFPA 58, incorporated by
reference in 41 Ill. Adm. Code 174.210, and shall also provide collision
protection that consists of one of the following options:
B2) steel or concrete bollards;
C3) raised sidewalks that are at least 5 inches tall at the face with the
cabinet set up so the distance from the face of the raised sidewalk
to the front of the cabinet is at least 40 inches. This measurement
may also include an additional bumper guard to reach the required
40 inches. Raised sidewalks may also consist of curbs or parking
bumper guards; or
D4) any other arrangement certified by a Licensed Professional
Engineer in accordance with national codes of practice and
accepted engineering practices and approved in advance by OSFM.A1) guardrails; |
Facility |
Miscellaneous |