1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose on dispenser 1 gasoline. Do Not use that dispenser hose until a new one is installed. |
Facility |
Miscellaneous - Emergency shut off switch at the control station requires a sign installed.
175.210 d) 3) Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
1, 2 |
Miscellaneous - Tank 1 and 2 vapor cap is missing. Replace both vapor caps. |
1, 2, 3 |
Triennial spill prevention equipment testing not completed. - All spill buckets require triannual testing. Passing results shall be entered on OSFM portal. |
1, 2, 3 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All STP and UDC sumps require triannual testing. Passing results shall be entered on OSFM portal. |
1 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Remove the liquid from the STP sump |