Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2033929
Status: Active
Facility Name: Circle K #6723
Address: 164 South Randall/Main
Batavia, IL 60510
County: Kane
Property Parcel: 12-21-158-002
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002401
Green Tag Issue Date: 1/5/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/5/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1995
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250330 (Pending)    Issue Date: 2/6/2025    Expiration Date: 4/7/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.
Facility Fire Extinguishers - Past due for annual testing - 2 extinguishers are past the annual test date.

NOV Number: E0020250331 (Pending)    Issue Date: 2/6/2025    Expiration Date: 4/7/2025    View NOV Form

Tanks Violation
1, 2 Dispensers - hoses cracked, split or worn and require replacement - Main hose has cracked and needs to be replaced.
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and maintenance plan needs to be updated and put in compliance book.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency procedures plan needs to be updated and put in compliance book.
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/16/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 12/8/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/8/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/6/2024 8/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/6/2024 8/6/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/6/2024 8/6/2025
Overfill Prev Device Overfill Drop Tube Valve 10/10/2024 10/10/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 1/25/2024 1/25/2027
Leak Detect - Piping Sump Sensor 8/6/2024 8/6/2025
Spill Contain Device Double Wall Spill Bucket 10/10/2024 10/10/2027
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/6/2024
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 3/15/2022



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/16/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 12/8/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/8/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/6/2024 8/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/6/2024 8/6/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/6/2024 8/6/2025
Overfill Prev Device Overfill Drop Tube Valve 10/10/2024 10/10/2027
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 1/25/2024 1/25/2027
Leak Detect - Piping Sump Sensor 8/6/2024 8/6/2025
Spill Contain Device Double Wall Spill Bucket 10/10/2024 10/10/2027
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 8/6/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/25/2024 1/25/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/6/2024 8/6/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/25/2024 1/25/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/6/2024 8/6/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/25/2024 1/25/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/6/2024 8/6/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/25/2024 1/25/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/6/2024 8/6/2025

MFD Motorfuel Dispensing Forms