Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2032954
Status: Active
Facility Name: Public Works Fleet Services
Address: 2405 Pembroke Avenue Hoffman Estates, IL 60195
County: Cook
Property Parcel: 07-06-102-008-0000
Facility Type: City / Town
Owner Type: Municipal
Green Tag Decal: Z004090
Green Tag Issue Date: 8/14/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Village of Hoffman Estates
Owner Address: 1900 Hassell Road Hoffman Estates, IL 60196
Owner Status: Current Owner / Operator
Purchase Date: 6/1/1991
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/7/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 8/14/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0006904 Village of Hoffman Estates Current Owner / Operator 6/1/1991

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00040-2026UPG Upgrade Approved / Issued 1/9/2026 1/9/2026 7/9/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260110 (Pending)    Issue Date: 1/6/2026    Expiration Date: 3/7/2026    View NOV Form

Tanks Violations
2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/14/1991 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 11/7/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/7/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Drop Tube Valve 8/5/2025 8/5/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/5/2025 8/5/2028
Tank Fiberglass Double Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 7/19/2024
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 8/5/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/14/1991 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 11/7/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/7/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Ball Float Vent Valve 7/22/2022 7/22/2025
Overfill Prev Device Overfill Drop Tube Valve 8/5/2025 8/5/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/5/2025 8/5/2028
Tank Fiberglass Double Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 7/19/2024
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 8/5/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found