Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2032485
Status: Active
Facility Name: Centegra Memorial Medical Center - Main
Address: 3701 Doty Road
Woodstock, IL 60098
County: McHenry
Property Parcel:
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z003731
Green Tag Issue Date: 1/23/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Northwestern Memorial Healthcare
Owner Address: 251 E. Huron
Chicago, IL 60611
Owner Status: Current Owner
Purchase Date: 1/1/1995
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/15/2025

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0010086 Northwestern Memorial Healthcare Current Owner 1/1/1995
U0021997 Woodstock Memorial Hospital Former Owner 11/18/1993

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: State Removed Date:
OSFM First Notify Date: 5/26/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 11/19/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/19/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 1/8/2024 1/8/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 1/8/2024 1/8/2025
Overfill Prev Device Overfill Drop Tube Valve 1/17/2023 1/17/2026
Piping Flexible Double Wall A.P.T. Poly Tech P200SC N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech P100SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 1/17/2023 1/17/2026
Tank Fiberglass Double Wall Owens Corning Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test Pass 5/28/2020
Piping Flexible Double Wall A.P.T. Poly Tech P100SC Precision Test Pass 5/28/2020
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test Pass 5/28/2020
Tank Fiberglass Double Wall Owens Corning Brine Filled Precision Test (Tank) Pass 1/17/2023



Tank Number 2

Capacity: 2500 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/26/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 11/19/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/19/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 1/8/2024 1/8/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 1/8/2024 1/8/2025
Overfill Prev Device Overfill Drop Tube Valve 1/17/2023 1/17/2026
Piping Flexible Double Wall A.P.T. Poly Tech P100SC N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech P200SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 1/17/2023 1/17/2026
Tank Fiberglass Double Wall Owens Corning Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Secondary Containment Steel primary Precision Test Fail 9/5/2019
Piping Fiberglass Single Wall Piping Ameron Precision Test Pass 5/28/2020
Piping Flexible Double Wall A.P.T. Poly Tech P100SC Precision Test Pass 5/28/2020
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test Pass 5/28/2020
Tank Fiberglass Double Wall Owens Corning Brine Filled Precision Test (Tank) Pass 1/17/2023