| 3 |
Miscellaneous - Vapor caps need to be replaced. They are not functioning. |
| 4 |
Miscellaneous - Premium STP sump sensor is lying down on the bottom of the sump. |
| 4 |
Miscellaneous - Vapor caps need to be replaced. They are not functioning. |
| 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 3 |
Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. |
| 3, 4 |
Tank monitor does not appear to function properly and requires maintenance. - ATG is in warning alarm Software Module Warning. CSLD tank testing is not functioning. |
| 3, 4 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Both STP and all UDC sumps need triannual testing. |