Notice of Violations (Current)
NOV Number:
E0020241702
(Formal)
Issue Date:
6/18/2024
Expiration Date:
8/17/2024
View NOV Form
| Tanks |
Violations |
| 1, 2, 3, 4 |
Failed to Empty the Tank to 1" or Less - Tank(s) is/are currently not in service and shall be pumped down to one inch or less of product. |
| 1, 2, 3, 4 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year |
| Facility |
Submit Notification Form for Ownership Change - Submit OSFM Notification Form showing change in facility ownership, complete and submit the online Notification for Underground Storage Tanks form which can be found at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
| 1, 2, 3, 4 |
Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing all tanks in Temporarily Out of Use status. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. |
NOV Number:
E0020261613
(Pending)
Issue Date:
6/18/2026
Expiration Date:
8/17/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Failed to Empty the Tank to 1" or Less - Tank 1 contains 26" of fuel.
Tank 2 contains 16" of fuel.
Unable to access Tank 3 fill pipe.
Unable to locate fill pipe for tank 4. |
| 1, 2, 3, 4 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year |
| Facility |
Submit Notification Form for Ownership Change - Submit OSFM Notification Form showing change in facility ownership, complete and submit the online Notification for Underground Storage Tanks form which can be found at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
9500 |
|
Petroleum Use: |
None |
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/17/1992 |
|
Abandoned Material: |
|
| Current Age: |
47 |
|
Abandoned Date: |
|
| Install Date: |
5/1/1979 |
|
Red Tag Issue Date: |
7/11/2022 |
| Last Used Date: |
7/20/2022 |
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300j |
5/1/2020 |
5/1/2021 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/7/2018 |
5/7/2021 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/17/2018 |
5/17/2021 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/17/1992 |
|
Abandoned Material: |
|
| Current Age: |
47 |
|
Abandoned Date: |
|
| Install Date: |
5/1/1979 |
|
Red Tag Issue Date: |
7/11/2022 |
| Last Used Date: |
7/20/2022 |
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300j |
5/1/2020 |
5/1/2021 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/7/2018 |
5/7/2021 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/17/2018 |
5/17/2021 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
2000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/17/1992 |
|
Abandoned Material: |
|
| Current Age: |
47 |
|
Abandoned Date: |
|
| Install Date: |
5/1/1979 |
|
Red Tag Issue Date: |
7/11/2022 |
| Last Used Date: |
7/20/2022 |
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300j |
5/1/2020 |
5/1/2021 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/7/2018 |
5/7/2021 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/17/2018 |
5/17/2021 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
500 |
|
Petroleum Use: |
None |
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/17/1992 |
|
Abandoned Material: |
|
| Current Age: |
47 |
|
Abandoned Date: |
|
| Install Date: |
5/1/1979 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
7/20/2022 |
|
Fee Due: |
$0.00 |
| Product Date: |
5/1/1979 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Gravity Feed |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Gravity Feed |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300j |
5/1/2020 |
5/1/2021 |
|
Overfill Prev Device
|
Less than 25 gallon fills |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping Ameron |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
5/17/2018 |
5/17/2021 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found